WATFULMake every watt count.Browse calculators
METHOD DC resistive drop modelSTATUS v1 calculatorHow we calculateTransparent formula · editable assumptions · shareable result

Cable Voltage Drop Calculator

How much voltage your cable run loses — and the cross-section that keeps the drop inside the 3% planning guideline.

Inputs

Load power at 12 V: 240 W

Results update as you type

Result

Voltage drop
7.3%
0.88 V lost · 11.13 V at the load
Over the 3% guideline
10 mm² keeps this run under 3%.
Also check the cable's ampacity rating — drop is not the only limit.
Voltage drop0.88 V
Power lost in cable17.5 W
For ≤ 3% use≥ 10 mm²
Drop = 2 × length × current × resistivity ÷ cross-section
2 × 5 m × 20 A × 0.0175 ÷ 4 mm² = 0.88 V (7.3%)
What this assumes
  • DC circuit — the factor 2 covers the return conductor.
  • Conductor at ~20 °C; resistance rises when cables run warm.
  • Copper ρ = 0.0175, aluminium ρ = 0.0286 Ω·mm²/m.
  • The 3% guideline is a planning figure, not a safety limit.

Matching gear

No paid placements
10 mm² tinned copper battery cableSized for ≤ 3% drop at 20 A on this run

Tinned strands resist corrosion in damp installations; verify the cable's ampacity rating covers your current too.

10 mm² cable lugs + heat shrinkCrimped, not soldered, for high-current DC

A poor termination adds more resistance than metres of correctly sized cable.

These are generic product classes matched to your inputs, not brand endorsements. If retailer links are added in the future, they will be clearly marked as affiliate links.

Cross-section comparison

CableDropVerdict
1.5 mm²19.4%over
2.5 mm²11.7%over
4 mm²7.3%over
6 mm²4.9%over
10 mm²2.9%≤ 3% ✓
16 mm²1.8%≤ 3% ✓
25 mm²1.2%≤ 3% ✓
35 mm²0.8%≤ 3% ✓

Click a row to load it into the calculator.

Questions

Why is the length doubled?

Current flows to the load and back, so a 5 m run has 10 m of conductor resisting it.

Why does 12 V suffer the most?

The same load needs four times the current at 12 V as at 48 V, and the same volt of drop is a four times larger share of the system voltage.

Is 3% a hard limit?

No — it is a common planning guideline for critical circuits. Some circuits tolerate 10%, but sensitive loads and charging circuits benefit from staying low. Ampacity (heat) is the actual safety limit.

How voltage drop is calculated

A cable is a resistor: drop = 2 × length × current × material resistivity ÷ cross-section. The factor two is there because current travels to the load and back. For example, 20 A through 5 m of 4 mm² copper drops 0.88 V — 7.3% of a 12 V system, well over the 3% planning guideline, and 17.5 W turned into heat along the way. The same run in 10 mm² drops 2.9% and passes.

Drop is not the only limit

This calculator answers "will my load see enough voltage?" — it does not answer "is this cable safe?". Every cable also has an ampacity rating (how much current it can carry without overheating) that depends on insulation, bundling and ambient temperature, and every DC circuit needs a correctly sized fuse at the battery end. Check both against your cable's datasheet and local rules.

Why system voltage matters so much

SystemCurrent for 1,000 WDrop in 5 m of 10 mm²
12 V83 A1.46 V = 12.2%
24 V42 A0.73 V = 3.0%
48 V21 A0.36 V = 0.8%

This is the practical reason bigger inverters use higher system voltages — see the Inverter Sizing calculator for the battery-side currents involved.

Methodology

The calculator UI, the cross-section table and the displayed formula all call the same calculation function. Resistivity values and the guideline come from the sources below.

Sources for the default assumptions
  • Copper resistivity ≈ 0.0175 Ω·mm²/m, aluminium ≈ 0.0286 Ω·mm²/m (20 °C) Standard electrical engineering reference values (IEC 60228 conductor classes)
  • ≤ 3% drop guideline for critical DC circuits Common marine and off-grid wiring practice, e.g. ABYC guidance (3% critical / 10% non-critical)
  • Ampacity must be checked separately Cable manufacturer datasheets and local electrical codes

Assumptions last reviewed on 26 August 2026. If a source disagrees with your battery or equipment datasheet, trust the datasheet.

Formula visibleThe equation is not a black box.
Assumptions editableUsers can change material and sizes.
One calculation sourceUI, examples and formula use the same model.
No account requiredCore tools work without signing up.